How to determine whether the remote module is connected through the program

Siemens PLC through the DeviceStates function block to judge

Mitsubishi L series PLC cc-Link ief basic

SM1704 judges the network status. Each station is judged by SD1704.0-1704.F and SD1705.0-SD1705.F

EtherCAT bus

Beofu PLC variable judgment: WcState=0,State=8 module bus connection

 


How to output PN Agreement Siemens PLC STOP mode remote module?

Output disconnect


Communication rate between EX series modules

6MB/S

What does the PROFINET module support

RT and MRP are supported


Communication rate setting of CC-Link module and fixed station logic station problem

Fixed logic stations: 4 stations

Variable logic station: 1-4 stations can be configured

EX series module is a remote equipment station, the number of occupying stations can be set 1-4 stations.

FS FS1 series is a remote IO station, occupying 1 station. Dip switch The value ranges from 0 to 4


https://www.welllinkio.com/images/admin/upload/20220329/09de5a16dcce16fbe47f40076da955ee.png

Communication rate setting of CC-Link module and fixed station logic station problem

https://www.welllinkio.com/images/admin/upload/20220329/3c4069025082262535fe065ad92d14ff.png


https://www.welllinkio.com/images/admin/upload/20220329/e26599ea7f41b1774a92a475fc9c1553.png


https://www.welllinkio.com/images/admin/upload/20220329/6a3df61b178ea060769f0d3436c917d8.png


Fixed logic stations: 4 stations

Variable logic station: 1-4 stations can be configured

EX series module is a remote equipment station, the number of occupying stations can be set (1-4 stations).


EX series supports analog range

Voltage type: 0-10V, 0-5V; ±10V, ±5V

Current type: 0-20mA, 4-20mA


The above ranges support 12BIT and 16BIT resolutions


Whether PROFINET and EtherCAT have the function to set the output state of broken line

The output state of the module can be configured after the bus is disconnected:

1. Keep the state before disconnection

2. Output 0

3. Output 1


What Agreement requires a description file?

PROFINET: Install the GSD file

EtherCAT: requires an XML file to be installed

CC-Link IE Field Basic: Install the cspp file

DeviceNet: Installs the EDS file

EtherNet/IP: Install the EDS file

CC-Link: Do not need to install the description file and only need to set the DIP switch


EX series power problem

EX adapter power supply is divided into:

System power supply: Provides system power for the expansion module and processes communication.

I/O load power supply: Supplies power to the sensor solenoid valve on the expansion module.

When the power of the customer's power adapter is sufficient:

The system power supply provides a maximum of 2A current.

The I/O load power supply provides a maximum of 10A current.

For example, the customer needs to drive 100 solenoid valves, and the coil current of the solenoid valve is 100 mA. When output is performed simultaneously, the current is 100*100ma=10A. Add a power module.

https://www.welllinkio.com/images/admin/upload/20220329/cddcce37d5b15929cc0723550eca378b.png

System and I/O power module: EX-0100