master module

SDEC-8IOL-M12-00

Order number:
07-01-03

Specification description:EtherCAT 8-channel IO-Link Master Coupler (M12 connector)

Product details

Data download

Signal input

Signal type:

Signal level:

Single channel current consumption:

Port protection (input):

Input characteristic:

Electrical isolation:

Signal output

Signal type:

Rated level:

Single channel rated current:

Port protection (output):

Electrical isolation:

General parameter

Class of protection:

Operating temperature:

Storage temperature:

Basic parameter
Protection gradeIP67(Bolted condition)
Appearance materialPA6+gf30%
Overall dimension66×221×29mm
Storing temperature-40℃…+85℃
Working temperature-25℃…+70℃
Power supply parameter
Power supply interface port type2×7/8” 5pin,Needle end+Hole end
US Standard voltage24 VDC (18…30 VDC)
US Current summation5A
UA Standard voltage24 VDC (18…30 VDC)
UA Current summation8A
Rated power consumption45mA
Electrical isolationUS and UA: 24V isolation, 0V isolation
Technical parameter
Communication protocolEtherCAT
Bus communication interface port type2×M12 D-code 4pin,Hole end
Maximum transmission distance100 m
Communication rate10/100 Mbit/s
Digital input16×PNP,type 3
Digital output end8×PNP
Input/output configurableYes
IO-link versionV1.1.3
IO-link Transmission rateCOM1, COM2 , COM3( 4.8 kbps\38.4 kbps\230.4 kbps)
IO-link port numbers/type8×CLASS A
Signal connection interface type8×M12 D-code 5pin,Hole end
Maximum distance to communicate with slave station20m
External 24V power supply current of IO-link port (Pin1)2A
Fault diagnosisSupport



name
date
dowload
User's Manual of SD Series IP67 IO-Link
2024-01-16
Selection Manual of SD Series IP67 IO-Link
2024-01-16